+ | ====== Air volumes ====== | ||
+ | ===== Too much air is also undesirable! ===== | ||
+ | |||
+ | ==== How much air is acceptable? ==== | ||
+ | |||
+ | With a [[planning: | ||
+ | |||
+ | Scientific studies have been carried out regarding **additional ventilation through windows** in Passive Houses during the heating period. Although this still occurs sometimes, it is becoming less and less common (as it is an old habit from the times when the occupants still lived in their old homes without ventilation systems), therefore it is not energy-relevant or practical! | ||
+ | |||
+ | Of course, it is possible to transfer even more air – and in theory, in the case of unlimitedly high air change rates, to achieve the quality of the external air, but in reality, noise caused by the air flow and draughts would have a restrictive effect (apart from the energy expenditure for transporting the air and the ventilation heat losses). Low indoor air humidity is the primary limiting factor if no humidification is planned for (increased effort for maintenance, | ||
+ | \\ | ||
+ | |||
+ | ==== Adjustment of the air volumes by the user ==== | ||
+ | |||
+ | {{: | ||
+ | * Experience with operation and evaluations of measured data (e.g. evaluation of the switch position during operation in the multi-storey building in Kassel Marbachshöhe) have shown that the systems are almost always operated at the " | ||
+ | |||
+ | * Even in single-family houses, the air volumes are only adjusted for longer periods of absence. | ||
+ | Nevertheless, | ||
+ | purge ventilation level "Party Ventilation" | ||
+ | \\ | ||
+ | |||
+ | ==== Automatic adjustment of air volumes? ==== | ||
+ | |||
+ | As early as 1991, in the first Passive House in Darmstadt Kranichstein a moisture and CO2-controlled ventilation system with air volumes shifting between the ground floor and the sleeping area in the upper floor was installed and operated; the objective was to reduce air volumes while optimising air quality at the same time. | ||
+ | |||
+ | The conclusion from today' | ||
+ | \\ | ||
+ | |||
+ | ==== Planning and dimensioning the system – over-dimensioning can lead to problems for lower air volumes! ==== | ||
+ | |||
+ | First of all, the linear characteristics of the ducting network have to be determined by dimensioning the duct cross-sections and the loss of pressure including that of all installations. | ||
+ | * Based on these linear characteristics, | ||
+ | |||
+ | * The device must still be able to transport the air flows necessary for purge ventilation (not with maximum efficiency as the operation periods in the purge ventilation mode are relatively short), and it must also be possible to achieve the minimum output of 0.3 1/h. | ||
+ | |||
+ | This is exactly what the problem is with** over-dimensioning**: | ||
+ | \\ | ||
+ | |||
+ | ==== More is better? | ||
+ | |||
+ | The size of the unit should be chosen carefully so that even small air flow rates can be transported and the air volumes should be dimensioned to remove not only pollutants but also to get rid of moisture from humidity sources. In contrast, the dimensioning of ducts and installations will only be limited by the costs and the space requirements. With a duct length of about 1 Pa/m in normal operation mode, it is possible to reach a good compromise - the system will be even more efficient with smaller air flows.\\ | ||
+ | \\ | ||
+ | ==== Future developments ==== | ||
+ | |||
+ | In the future, ventilation systems will become even better with regard to user comfort, efficiency and costs; even today these systems are well-engineered and constitute the main components for providing comfort and good air quality in modern (or refurbished) buildings.\\ | ||
+ | \\ | ||
+ | ===== Air volumes and air humidity are closely related ===== | ||
+ | |||
+ | The level of relative indoor air humidity in internal spaces depends substantially on both of the following influencing parameters: | ||
+ | |||
+ | * the intensity of the internal humidity sources (e.g. plants, cooking, drying clothes, | ||
+ | |||
+ | * the amount of fresh air supplied from outside. | ||
+ | |||
+ | The water vapour from internal sources of humidity is diluted with the fresh incoming external air. It makes no difference whether the external air enters through gaps, windows or a ventilation system (as long as no humidification or dehumidification takes place), or whether the air is heated (e.g. by a heat recovery system) – the mass of the water content in the air flow does not change in any of these situations.\\ | ||
+ | \\ | ||
+ | ==== With “normal ventilation” ==== | ||
+ | |||
+ | This diluting effect is even greater in the winter as cold external air only contains a very small amount of water vapour (for example, at -5°/90% only about 3 g per cubic metre of air, see following illustration).\\ | ||
+ | \\ | ||
+ | |{{: | ||
+ | |//**The amount of water contained in cold air is very small (in the example:\\ | ||
+ | 3 g/m³) and that is already 90 % of the total quantity of moisture which \\ | ||
+ | the air can take up at -5°C (humidity saturation at -5°C).\\ | ||
+ | Warmer air can hold a significantly greater amount of water vapour, | ||
+ | e.g. up to 17.3g at 20°C/m³. If cold air enters the room and warms up\\ | ||
+ | to 20°C, the 3g of water per m³contained in it will be equivalent to \\ | ||
+ | a relative humidity of only 17.6%.**// | ||
+ | \\ | ||
+ | If this cold air enters the room and is warmed to 20°C, then its relative humidity will only be 17.6% - as long as additional water vapour from internal sources is not added to the indoor air. With ordinary moisture sources in the household (330 g/h – varying individually) and “standard“ ventilation (120 m³/h in the example - DIN 1946 is applicable here), a **relative indoor air humidity of 33.5 %** results under these conditions. Usually, this level is comfortable enough if the air is reasonably clean (containing less dust).\\ | ||
+ | \\ | ||
+ | |{{: | ||
+ | |//**With “normal ventilation” of 120 m³/h, the moisture released into\\ | ||
+ | the house is diluted so much that under the given external\\ | ||
+ | air conditions depicted here, the relative humidity of the room\\ | ||
+ | reaches slightly more than 33%. Usually this is acceptable.\\ | ||
+ | (Air quantity per person 30 m³/h based on DIN 1946,\\ | ||
+ | air changes based on air volumes of about 0.37 h< | ||
+ | \\ | ||
+ | The greater the incoming quantity of external air is, the lower the relative indoor air humidity will be inside.\\ | ||
+ | \\ | ||
+ | |||
+ | ==== With “increased ventilation” ==== | ||
+ | |||
+ | |{{: | ||
+ | |//**With “increased ventilation” of 240 m³/h, the moisture released into\\ | ||
+ | the house is diluted even more. Relative humidity drops to\\ | ||
+ | about 27%. This is generally perceived as being too dry.\\ | ||
+ | External air volumes of 60 m³/h per person are therefore considered\\ | ||
+ | extensive with regard to the moisture balance\\ | ||
+ | (air changes based on air volumes of 0.75 h< | ||
+ | \\ | ||
+ | |||
+ | ==== Low indoor air humidities ==== | ||
+ | |||
+ | With standard ventilation, | ||
+ | \\ | ||
+ | |{{: | ||
+ | |//**Based on experience (measurements in various Passive Houses),\\ | ||
+ | external air volumes of 80 m³/h, equivalent to 20 m³/h per person,\\ | ||
+ | are still sufficient for indoor air hygiene.\\ | ||
+ | At this rate, the level of air humidity in the house settles at 41%.**// | ||
+ | \\ | ||
+ | **Air changes will then be only about 0.25 h< | ||
+ | \\ | ||
+ | **No-one should have to ventilate beyond their comfort level in terms of air humidity**. | ||
+ | * Conventional ventilation designers tend to dimension the air volumes of home ventilation systems as rather high. At times, air change rates of 0.5 or even 0.8 are considered to be necessary, - especially in order to keep the indoor air humidity low in winter, thus reducing the risk of condensation and the associated mould growth. | ||
+ | |||
+ | * In Passive Houses, both problems do not occur anyway, because due to the good level of thermal protection, all interior surfaces of external components are so warm that even at 60% indoor air humidity, condensation cannot occur. Therefore, the external air quantity can be decreased slightly in cold periods, particularly if indoor air humidity is felt to be too low by the occupants. **Ventilation system air changes between 0.3 and 0.4 are " | ||
+ | \\ | ||
+ | **Remedying low indoor air humidities**: | ||
+ | |||
+ | * Adjust air volumes to lower levels | ||
+ | |||
+ | * Add sources of moisture in the living areas (e.g. plants) | ||
+ | |||
+ | * Keep the home as dust-free as possible: clean more often using a vacuum cleaner equipped with a fine dust filter. | ||
+ | |||
+ | Incidentally, | ||
+ | With indoor air that is still perceived as sufficiently “humid”, | ||
+ | |||
+ | |||
+ | ===== See also ===== | ||
+ | |||
+ | [[planning: |